The HK1-08K-01A is an 8 kW factory accessory heat kit for packaged air conditioners and packaged heat pumps. It installs inside the unit’s electric-heat compartment and adds supplemental resistance heat when outdoor temperature drops or extra capacity is needed. Heating elements warm the supply air; the unit blower distributes it through the duct system.
A2L-approved components allow use with both R-454B and R-410A packaged equipment. The kit uses a 9-pin heater plug for factory-style connection, dual limit controls (main air limit plus backup limit), and a contactor for safe staged power. At 240 V it delivers about 23,816 BTU/h. Minimum airflow for a 40°F temperature rise is approximately 550 CFM. It is rated 208/230 V, single-phase, 60 Hz and can be wired as a single circuit or split across two circuits depending on the host unit.
Features & benefits
- 8 kW electric heat adds reliable backup or supplemental heating without a separate furnace.
- A2L-compliant construction is approved for R-454B and R-410A packaged units, so you can upgrade or replace heat on newer low-GWP equipment.
- Factory 9-pin plug and matching control-box harness speed installation and reduce wiring errors.
- Dual limit protection (primary air limit + backup limit) helps prevent overheating if airflow is restricted.
- Works as single-circuit or two-circuit supply (with optional breakers / single-circuit adapter) so you can match existing panel capacity.
- Zero-clearance to combustibles when installed per unit and kit instructions.
- Designed specifically for Nortek / Frigidaire / AireForce packaged AC and heat-pump cabinets—no field fabrication of element racks.
Capacity & electrical data
- Nominal capacity: 8 kW
- Heating output: ~23,816 BTU/h (240 V)
- Voltage: 208/230 VAC, 1-phase, 60 Hz
- Typical single-circuit MCA / MOP (varies by host unit): on the order of 39–43 A MCA and 40–45 A MOP at 208/230 V for smaller packaged models; always use the unit rating plate and installation tables.
- Minimum recommended airflow: ~550 CFM (for ~40°F rise)
- Circuit options: 1-circuit or 2-circuit (circuit breakers P/N 913554 and 4-pole single-circuit adapter P/N 913350 available separately)
Dimensions The HK1-08K-01A is an internal slide-in heater bank, not a standalone boxed appliance. It occupies the factory heat-kit opening in compatible packaged units. Physical envelope follows the unit’s electric-heat compartment (element plates, limits, and contactor mounted as shown in the HK1 installation instructions). Exact cabinet opening and mounting orientation depend on whether the packaged unit uses vertical or horizontal supply/return and small vs. large cabinet—see the HK1 Series installation manual for element position (limit toward bottom on vertical 8 kW installs; elements closest to the blower).
Compatibility Approved for field installation in Nortek / Frigidaire / AireForce packaged air conditioners and packaged heat pumps when listed in the HK1 application tables, including (examples from the official cross-reference):
- 1.5-ton single-phase packaged units such as (*)P94RD-018K
- 2-ton single-phase packaged units such as ()P94RD-024K / ()P95RD-024K
- Other P9 / Q-series and similar packaged AC and HP models listed for 8 kW HK1-08K-01A (typically 1.5–5 ton single-phase 208/230 V equipment)
Confirm the exact packaged unit model against the HK1 Series application tables (Tables 5–7 in the installation instructions) before ordering. Not for use as a substitute H3HK kit on R-454B equipment—the H3HK line is not A2L approved. Must be installed by a licensed HVAC technician; improper installation voids warranty.
- 8 kW Supplemental Heat — adds electric resistance heat to packaged ACs and heat pumps
- A2L Compliant — approved for use with A2L refrigerant systems
- Installs Inside the Unit — mounts in the packaged unit's electric-heat compartment
- Built-In Limit Controls — protects the unit and the home
Genuine OEM parts
Easy online ordering
30-day hassle-free returns